Welcome to ZheJiang Mingch Electrical Co.,Ltd.

Galleon 33 Home / On Line three phases UPS / Galleon 33

Galleon 33

•True double-conversion
•DSP technology guarantees high performance
•Output power factor 0.8
•Wide input voltage range (110-300 VAC)
•Active power factor correction in all phases
•50Hz/60Hz frequency converter mode
•Eco mode operation for energy saving (ECO)
•Accepts dual power inputs
•Emergency power off function (EPO)
•Generator compatible
•SNMP+USB+RS-232 multiple communications
•3-stage extendable charging design for optimized battery performance
•Adjustable battery numbers
•Maintenance bypass available
•Optional N+X parallel redundancy
•Optional isolation transformer offers full isolation and complete common mode noise rejection

Technical Parameters

MODEL  Galleon 3/3-10K (L) Galleon 3/3-15K (L) Galleon 3/3-20K (L) Galleon 3/3-30K (L)
PHASE 3 phase in / 3 phase out
CAPACITY 10000 VA / 8000 W 15000 VA / 12000 W 20000 VA / 16000 W 30000 VA / 24000 W
INPUT
Nominal Voltage 3 x 400 VAC (3Ph+N)
Voltage Range  305-478 VAC (3-phase) @ 100% load
190-520 VAC (3-phase) @ 50% load
Frequency Range
46~54 Hz or 56~64Hz
Power Factor ≧ 0.99  @ 100% load
OUTPUT
Output Voltage 3 x 400 VAC (3Ph+N)
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Synchronized Range) 46~54Hz or 56~64Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦ 2 % THD (Linear Load)  ≦ 5 % THD (Non-linear Load)
Transfer Time AC mode to Battery mode zero
Inverter to Bypass zero
Waveform (Batt. Mode) Pure Sine Wave
EFFICIENCY
AC Mode 89% 89% 89% 90%
Battery Mode 86% 88% 87% 89%
BATTERY
Standard Model Battery Type 12 V / 9 AH
Numbers 20 pcs (18 – 20 adjustable)** 20 pcs (18 – 20 adjustable)**x 2 strings 20pcs (18-20adjustable)** x 3 strings
Typical Recharge Time 9 hours recover to 90% capacity
Charging Current (max.) 1A 2A 2A 4A
Charging Voltage 273 VDC ± 1%(based on 20 pcs batteries)
Long-run Model Battery Type Depending on the capacity of external batteries
Numbers
Charging Current (max.) 4A 4A 4A 12A
Charging Voltage 273 VDC ± 1%(based on 20 pcs batteries)
INDICATORS
LCD Panel UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
ALARM
Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
PHYSICAL
Standard Model Dimension, D X W X H (mm) 815 x 250 x 826 815 x 250 x 826 815 x 250 x 826 815 x 300 x 1000
Net Weight (kgs) 109 164 164 233.5
Long-run Model Dimension, D X W X H (mm) 592 x 250 x 826 592 X 250 X 826 592 X 250 X 826 815 x 250 x 826
Net Weight (kgs) 38 40 40 64
ENVIRONMENT
Operation Humidity 0-95 % RH @ 0- 40°C (non-condensing)
Noise Level Less than 60dB @ 1 Meter Less than 65dB @ 1 Meter
MANAGEMENT
Smart RS-232/USB Supports Windows® 2000/2003/XP/Vista/2008, Windows®  7/8, Linux, Unix, and MAC
Optional SNMP Power management from SNMP manager and web browser

* L means long-run model
*When using internal batteries from 18-19, the unit will de-rate according to below formula: P=Prating X N/20
* Product specifications are subject to change without further notice

SEND US A MESSAGE

If you are interested in our products, please don’t be hesitated to contact us. Please send mail to info@mingch.com.cn, or leave your message at the following form. We will contact you within 24 hours. Thank you for your enquiry.